Inspector — hall

Can this floor survive the next generation?

floor_load = rack_mass / footprint = 2500 kg/m² ≈ 24.5 kN/m² · design rating 12 kN/m²
Floor loading limit12 kN/m²cited
Floor headroom-1276 kg/m²◌ derived
negative headroom — exceeds the design rating above
Contiguous racks2500◌ derived
Hopper — supported (enters at 30 kW)GB200 NVL72 — needs 120 kW per rackVera Rubin — needs 180 kW per rackannouncedKyber 600 kW — needs 600 kW per rackannouncedFeynman 1 MW class — needs 1000 kW per rackroadmap

Rack mass for this class is reported 1,360–1,553 kg side by side (vendor / literature · RR-04) — the maker publishes no weight. No standard publishes a forward design target either, so the line above is a derivation shown, not an authority cited.

Whether that is acceptable is a judgment this model does not make.